Specification - We need two compressors installing in separate locations, both to be installed in containers serviced with 3 phase power and heating. The footprint of each compressor should not exceed 800 x 1800 mm. Both compressors need to have desiccant dryers to minus 40PdP and filtration to 0.1 micron with oil separation and drain. Both compressors to have 270 litre air receivers. One compressor must be capable of delivering 7 cft pulse every 10 seconds at 5-7 bar (not exceeding 12 kW motor), and the other must be able to deliver 3.5 cft every 10 seconds (not exceeding 8 kW motor), for up to an hour at a time.